Application and energy saving of plate heat exchanger in data center

1, water cooling system
From 2005 to 2009, the Internet industry developed rapidly, and the demand for data services soared. Data centers with small scale and low power density had to bear a lot of IT equipment. At this time, the power density of the single cabinet has increased to 3~5kw, and the size of the data center has gradually increased. Medium-sized data centers with hundreds to thousands of cabinets have begun to appear. As the scale has grown, data center energy consumption has increased dramatically, and energy conservation issues have begun to receive attention.
The traditional air-cooled direct expansion system has lower energy efficiency than COP (Coefficient Of Performance). The COP in Beijing is about 2.5~3.0. The air-conditioning equipment consumes a lot of power and accounts for a high proportion of the overall power consumption of the data center. Moreover, with the expansion of installed capacity, the installation position of the air-cooled condenser reserved in the original data center building is seriously insufficient, and the noise disturbance problem is prominent, which restricts the expansion of the data center. At this time, the chilled water system widely used in office buildings began to be gradually applied to the data center refrigeration system. Since the COP of the chiller can reach 3.0~6.0, the large centrifugal chiller is even higher, and the chilled water system can greatly reduce the data. The center operates energy consumption.
The chilled water system is mainly composed of a chiller, a cooling tower, a chilled water pump, a cooling water pump, and a chilled water type air conditioner end. The system adopts centralized cold source, the cooling efficiency of the chiller is high, and the cooling tower is placed in a flexible position, which can effectively control the noise and benefit the aesthetic appearance of the building. After reaching a certain scale, it has more construction cost and maintenance cost than the direct evaporative system. Economic advantage.
Cooling system
The end of the air-conditioning system used in the chilled water system is a chilled water-type precision air conditioner, and its single cooling capacity can reach more than 150kw. The air supply mode and the previous air-cooled direct expansion system have not changed much, only the cooling medium in the end changes. The air conditioning equipment is still far away from the IT heat source, and mainly relies on the air-conditioning fan to deliver air to maintain the airflow organization.
 2, plate heat exchanger and water cooling system natural cooling
From 2010 to the present, with the development of data center cooling technology and people's further attention and pursuit of data center energy consumption, the concept of natural cooling has gradually been applied to the data center.
In the northern part of China, the outdoor temperature is lower in winter, and the water side natural cooling system is used. In winter, there is no need to open the mechanical refrigeration unit, and the cooling tower and the plate heat exchanger are used to “free” to obtain the cold source, thereby reducing the energy consumption of the data center. The water side natural cooling system is a set of plate heat exchangers and related switching valve groups above the original chilled water system. The chiller mechanical cooling is still used in high temperature weather, and the low temperature cooling water prepared by the cooling tower is used in the low temperature season. The high-temperature chilled water is exchanged for heat. In the transitional season, the lower-temperature cooling water and the higher-temperature chilled water are pre-cooled before entering the chiller, and the chiller load and running time can be reduced.
Principle of natural cooling system for water cooling system
 
The temperature of chilled water in traditional data centers is generally 7/12 °C. For example, in Beijing, natural cooling can be used 39% of the year. If the chilled water is raised to 10/15 °C, the natural cooling time will be extended to 46%. At the same time, due to the increase of evaporation temperature, the COP of the chiller can be increased by 10%. On the other hand, as the server withstands the increase in temperature, the chilled water temperature can be further increased, and the natural cooling time throughout the year will be further extended. At present, the domestic technology-leading data center has increased the chilled water temperature to 15/21 °C, and the natural cooling time can reach 70% or even longer.
2019/05/10 20:04:16 3705 Click

“深港汽车快通计划”在前海综合保税区启动 雅迪科技集团轮值总裁周朝阳:雅迪的长期主义|雅迪 因10GW项目长期未推进,一光伏上市公司被要求退还5.1亿财政补助|梧州市 兴业银行:“兴业转债”拟于12月29日付息 商务部公布对原产于欧盟的进口相关乳制品反补贴调查的初步裁定|欧盟 从“煤都”到“绿电”基地 大同晋北新能源基地赋能京津冀 午评:港股恒指涨0.2% 科指涨0.89% 黄金股普涨 半导体板块走强 四只新股集体下跌 iRobot易主中国“无冕之王”:杉川收购案或将改写全球扫地机格局 博纳影业12月22日龙虎榜数据|博纳影业 12月19日增减持汇总:龙芯中科等13家公司拟减持 无A股增持(表) 渠道先热: 资深代理商集体押注,OMOWAY自平衡智能电摩撬动千亿级市场 又一AI独角兽冲刺港股IPO,阿里腾讯跟投,员工平均95后 2026年计算机行业年度策略:从“+AI”到“AI+”,AI巨轮破浪前行(附下载)|计算机行业 超大现代完成发行合共3295万股配售股份 净筹约719万港元|超大现代 ODI备案手续完成批复 四维图新终成鉴智第一大股东 头皮健康重塑洗护行业新生态——诗裴丝斩获SIA2025年度大奖,印证国货科研实力 山子高科涨停,机构净买入2616.17万元,深股通净买入7428.57万元|深股通 博菲电气12月22日龙虎榜数据|证券 涂鸦智能发布2025年Q3财报:加速Physical AI创新,推动AI融入真实生活 商务部部长王文涛会见美国超威半导体公司董事会主席兼首席执行官苏姿丰 操盘必读:影响股市利好或利空消息