Application of plate heat exchanger in radiant heating and cooling

Radiation heating and cooling air conditioning systems have been used and developed in Europe and North America for many years. Unlike traditional convection air conditioning systems, radiative heat and heat transfer systems account for more than 50% of total heat exchange. The air conditioning system based on low-temperature radiation heat transfer works by inputting cold water of about 18 °C into the end of the radiation in summer to form a cold radiating surface; in winter, it provides hot water of about 45 °C to the end of the radiation to form a heat radiating surface, relying on Radiant heat exchange with the human body, furniture and the rest of the enclosure is cooled (heated). If the temperature of the hot and cold water supplied by the cold heat source is too low or too high to meet the radiation end temperature requirements, the plate heat exchanger or other methods (such as water mixing) are usually used to achieve the temperature of the cold (hot) medium. Claim.
First, the application in radiant cooling
When radiant cooling, the temperature of the cold water in the end of the radiation should not be too low, otherwise it will easily produce condensed water at the surface of the radiation, causing condensation. Generally, the method of controlling the temperature of the cold water inlet of the radiation end is adopted, so that the surface temperature of the radiation plate is higher than the air dew point temperature by 1 to 2 ° C to prevent condensation. The chilled water temperature (16-18 °C) used in radiant cooling systems is usually higher than conventional air conditioning systems (7 °C). The higher cold water temperature provides a choice for natural cold sources such as evaporative cooling (6-8 ° C), but It also makes the chilled water produced by the conventional chiller (the supply and return water temperature is 7/12 °C) can not directly meet the requirements of the radiant cooling system for the cold water temperature. Generally, the high temperature required for radiant cooling can be obtained by the method of mixing water. Cold water, but in order to prevent the cold water from directly entering the sensible heat exchange end (especially the capillary) and causing scale on the inner surface of the heat exchanger to block, the high-efficiency plate heat exchanger can be used to carry out the countercurrent heat exchange of the cold water produced by the chiller. Then send it to the sensible heat end. The inlet water temperature commonly used for sensible heat at the time of radiant cooling is 16 to 18 ° C, and the return water temperature is generally 21 to 23 ° C.
Second, the application in radiant heating
The application of plate heat exchanger in low temperature radiant heating is divided into two types: water-water heat exchange condition and steam-water heat exchange condition. When steam is used as the heat source, the steam must be low-pressure saturated steam. The pressure commonly used in engineering is: gauge pressure 0.3MPa or gauge pressure 0.4MPa, the steam temperature at this time is 144 ° C and 152 ° C. When hot water is used as the heat source, the hot water supply back water temperature is generally 95/70 °C. In radiant heating, the temperature of the hot water supplied to the end of the radiation should not be too high, generally not exceeding 60 ° C. The main reasons are:
1. Due to the large radiation area, the water temperature does not need to be too high to meet the room temperature design requirements;
2, the human body comfort requires the ground temperature can not be too high;
3. At higher water temperatures, the life of plastic pipes commonly used in radiant heating is greatly reduced. According to the different requirements of building insulation and occupants, the ground temperature is usually controlled within the range of 24 to 30 °C. Excessive temperature affects comfort and causes unnecessary waste. If the temperature is too low, heating requirements are not met.
In recent years, the state's requirements for building energy conservation have been continuously improved, and the degree of insulation of the envelope structure has become better and better, which has led to a continuous decrease in the actual use of water. Under the premise of common pipe diameter and pipe spacing, the actual required inlet water temperature is often lower than 50 °C. When the outdoor temperature is not too low, the inlet temperature of 30-40 °C can already have obvious heating effect. The inlet and outlet water temperature commonly used in low temperature radiant heating systems is usually 45/35 °C.
2019/05/10 20:08:59 3760 Click

AI亏损魔咒“破局者”,MiniMax四年跻身全球第一梯队,平均29岁的团队如何创造效率奇迹?|AI 牛市里的“掉队者”东阿阿胶:新增长极在哪? 独家 | 智谱今日启动PDIE,高增长与高投入并行,估值244亿|智能体 首程控股“陶朱新造局”赋能机器人产业加速落地|首程控股 东证荣誉 量化机房之迷 澳门举行“濠江忆荣光——纪念中国人民抗日战争胜利80周年暨澳门回归祖国26周年图片展” 收评:港股恒指涨0.43% 科指涨0.87% 黄金股普涨 半导体板块走强 今日四只新股集体收跌 连续突破记录 马斯克成史上首位身家7000亿美元富豪|美元|马斯克|特斯拉 广州地铁迎来通车“大年” 城市枢纽能级跃上新台阶 世界羽联世界巡回赛总决赛:冯彦哲/黄东萍夺得混双冠军 广东陆丰核电项目2号机组主体工程正式开工 广东江门新会区通报陈皮产地造假:将对6家涉事企业作出处理|广东省 板块异动 | 国产算力链资本与产业共振 CPO概念高开领涨A股|摩尔 从金融向善到践行公益:数禾科技的留守儿童关爱之路 极限施压下委内瑞拉民众的“曲线回家路” 宁夏银川:智慧医养下沉基层 织密全民健康保障网 创业板第三套上市标准再次被“激活”|创业板 美国签证审查严重拖长 谷歌和苹果建议外籍员工“别出美国” 参保人数突破330万!2026年度“北京普惠健康保”参保仅剩最后一周 知名上市药企,被重罚2560万!|贵州百灵 富国基金+中国船舶集团,全市场首只船舶ETF正式启航